Universal mounting foot, available for rails NS35 and NS32.
Static connection stability is strong.
Potential distribution with bridges.
Product number | JUT1-10 | JUT1-10PE | JUT1-10RD |
product type | Rail Terminals | Rail ground terminal | Rail ground terminal |
Mechanical structure | screw type | screw type | screw type |
layers | 1 | 1 | 1 |
Electric Potential | 1 | 1 | 1 |
connection volume | 2 | 2 | 2 |
Rated cross section | 10 mm2 | 10 mm2 | 10mm2 |
Rated current | 57A | 10A | |
Rated voltage | 800V | 800V | |
open side panel | yes | no | no |
grounding feet | no | yes | no |
other | for fuse size G/5x20 | ||
Application field | electricity, mechanical engineering, factory engineering, process industry, etc. | ||
color | gray, customizable | yellow and green | black, customizable |
line contact | |||
Stripping length | 10mm | 10mm | 10mm |
Rigid Conductor Cross Section | 0.5mm² — 16mm² | 0.5mm² — 10mm² | 0.5mm² — 10mm² |
Flexible conductor cross section | 0.5mm² — 10mm² | 0.5mm² — 6mm² | 0.5mm² — 10mm² |
Rigid Conductor Cross Section AWG | 20-6 | 20-8 | 24-6 |
Flexible Conductor Cross Section AWG | 20-8 | 20-10 | 24-6 |
thickness | 10.2mm | 10.2mm | 12mm |
width | 42.5mm | 42.5mm | 62mm |
high | |||
NS35/7.5 high | 47mm | 47mm | 57mm |
NS35/15 high | 54.5mm | 54.5mm | 64.5mm |
NS15/5.5 high |
Flame retardant grade, in line with UL94 | V0 | V0 | V0 |
Insulation Materials | PA | PA | PA |
Insulation material group | I | I | I |
standard test | IEC 60947-7-1 | IEC 60947-7-2 | IEC 60947-7-3 |
Rated voltage(III/3) | 800V | 800V | |
Rated current(III/3) | 57A | 10A | |
Rated surge voltage | 8kv | 8kv | 8kv |
Overvoltage class | III | III | III |
pollution level | 3 | 3 | 3 |
Surge Voltage Test Results | Passed the test | Passed the test | Passed the test |
Power frequency withstand voltage test results | Passed the test | Passed the test | Passed the test |
Temperature rise test results | Passed the test | Passed the test | Passed the test |
Surge Voltage Test Results | -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) | -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) | -40 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
Ambient temperature (storage/transport) | -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) | -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) | -5 °C — 70 °C (short term (up to 24 hours), -60 °C to +70 °C) |
Ambient temperature (assembled) | -5 °C — 70 °C | -5 °C — 70 °C | -5 °C — 70 °C |
Ambient temperature (execution) | -5 °C — 70 °C | -5 °C — 70 °C | -5 °C — 70 °C |
Relative Humidity (Storage/Transportation) | 30 % — 70 % | 30 % — 70 % | 25 % — 75 % |
RoHS | No excessive harmful substances | No excessive harmful substances | No excessive harmful substances |
Connections are standard | IEC 60947-7-1 | IEC 60947-7-2 | IEC 60947-7-3 |