The Push-in direct connection technology make the insertion forces reduced by up to 50 percent and tool-free wiring, enable the conductors to be inserted easily and directly.
Made from engineering flame retardants nylon PA66 with brass screw metal.
●The Push-in connection terminal blocks are characterized by easy and tool-free wiring of conductors with ferrules or solid conductors.
●The compact design and front connection enable wiring in a confined space.
●In addition to the testing facility in the double function shaft, all terminal blocks provide an additional test connection.
●With universal foot which can be installed on Din Rail NS 35.
●It can connect two conductors with ease, even large conductor cross sections are not a problem.
●Electric potential distribution can use fixed bridges in the terminal center.
●All types of accessories: End cover, End Stopper, Partition plate, marker trip, fixed bridge, insertion bridge, etc.
Details parameters: |
|||||
Product Image |
|
|
|
|
|
Product number |
JUT14-4/DK/GY |
JUT14-4/1-2//DK/GY |
JUT14-4/2-2//DK/GY |
JUT14-4/2/DK/GY |
JUT14-4 PE |
product type |
Rail wiring distribution block |
Rail wiring distribution block |
Rail wiring distribution block |
Rail wiring distribution block |
Rail wiring distribution block |
Mechanical structure |
Push-in spring connection |
Push-in spring connection |
Push-in spring connection |
Push-in spring connection |
Push-in spring connection |
layers |
1 |
1 |
1 |
2 |
1 |
Electric potential |
1 |
1 |
1 |
2 |
1 |
connection volume |
2 |
3 |
4 |
4 |
1 |
Rated cross section |
4 mm2 |
4 mm2 |
4 mm2 |
4 mm2 |
4 mm2 |
|
|
|
|
|
|
|
|
|
|
|
|
Rated current |
32A |
32A |
32A |
32A |
|
Rated voltage |
800V |
800V |
800V |
800V |
|
open side panel |
Yes |
Yes |
Yes |
Yes |
no |
grounding feet |
no |
no |
no |
no |
no |
other |
The connecting rail needs to install the rail foot F-NS35 |
The connecting rail needs to install the rail foot F-NS35 |
The connecting rail needs to install the rail foot F-NS35 |
The connecting rail needs to install the rail foot F-NS35 |
The connecting rail needs to install the rail NS 35/7,5 or NS 35/15 |
Application field |
Widely used in electrical connection, industrial |
Widely used in electrical connection, industrial |
Widely used in electrical connection, industrial |
Widely used in electrical connection, industrial |
Widely used in electrical connection, industrial |
color |
(gray)、(dark gray)、(green)、(yellow)、(cream)、(orange)、(black)、(red)、(blue)、(white)、(purple)、(Brown)、customizable |
(gray)、(dark gray)、(green)、(yellow)、(cream)、(orange)、(black)、(red)、(blue)、(white)、(purple)、(Brown)、customizable |
(gray)、(dark gray)、(green)、(yellow)、(cream)、(orange)、(black)、(red)、(blue)、(white)、(purple)、(Brown)、customizable |
(gray)、(dark gray)、(green)、(yellow)、(cream)、(orange)、(black)、(red)、(blue)、(white)、(purple)、(Brown)、customizable |
Green and Yellow |
|
|||||
Stripping length |
11mm |
11mm |
11mm |
11mm |
11mm |
Rigid Conductor Cross Section |
0.2-4mm² |
0.2-4mm² |
0.2-4mm² |
0.2-4mm² |
0.2-4mm² |
Flexible conductor cross section |
0.2-4mm² |
0.2-4mm² |
0.2-4mm² |
0.2-4mm² |
0.2-4mm² |
Rigid Conductor Cross Section AWG |
24-10 |
24-10 |
24-10 |
24-10 |
24-10 |
Flexible Conductor Cross Section AWG |
24-12 |
24-12 |
24-12 |
24-12 |
24-12 |
|
|||||
size (this is the dimension of the JUT14-4 carrying rail foot F-NS35 installed on the rail) |
|||||
thickness |
6.2mm |
6.2mm |
6.2mm |
6.2mm |
6.2mm |
width |
53.3mm |
67.5mm |
81.5mm |
78.3mm |
53.5mm |
high |
35.6mm |
35.6mm |
35.6mm |
47.5mm |
35.6mm |
NS35/7.5 high |
43.1mm |
43.1mm |
43.1mm |
55mm |
43.1mm |
NS35/15 high |
50.6mm |
50.6mm |
50.6mm |
62.5mm |
50.6mm |
NS15/5.5 high |
|
|
|
|
|
|
|||||
Material properties |
|||||
Flame retardant grade, in line with UL94 |
V0 |
V0 |
V0 |
V0 |
V0 |
Insulation Materials |
PA |
PA |
PA |
PA |
PA |
Insulation material group |
I |
I |
I |
I |
I |
|
|||||
IEC电气参数 IEC Electrical parameters |
|||||
测试标准 standard test |
IEC 60947-7-1 |
IEC 60947-7-1 |
IEC 60947-7-1 |
IEC 60947-7-1 |
IEC 60947-7-1 |
Rated voltage(III/3) |
800V |
800V |
800V |
800V |
|
Rated current(III/3) |
32A |
32A |
32A |
32A |
|
Rated surge voltage |
6kv |
6kv |
6kv |
6kv |
6kv |
Overvoltage class |
III |
III |
III |
III |
III |
pollution level |
3 |
3 |
3 |
3 |
3 |
|
|||||
Electrical performance test |
|||||
Surge Voltage Test Results |
Passed the test |
Passed the test |
Passed the test |
Passed the test |
Passed the test |
|
|
|
|
|
|
Power frequency withstand voltage test results |
Passed the test |
Passed the test |
Passed the test |
Passed the test |
Passed the test |
Temperature rise test results |
Passed the test |
Passed the test |
Passed the test |
Passed the test |
Passed the test |
|
|||||
environmental conditions |
|||||
Ambient temperature (operating) |
-60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
-60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
-60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
-60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
-40℃~+105℃(Depends on the derating curve) |
Ambient temperature (storage/transport) |
-25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) |
-25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) |
-25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) |
-25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) |
-25 °C - 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembled) |
-5 °C — 70 °C |
-5 °C — 70 °C |
-5 °C — 70 °C |
-5 °C — 70 °C |
-5 °C — 70 °C |
Ambient temperature (execution) |
-5 °C — 70 °C |
-5 °C — 70 °C |
-5 °C — 70 °C |
-5 °C — 70 °C |
-5 °C — 70 °C |
Relative Humidity (Storage/Transportation) |
30 % — 70 % |
30 % — 70 % |
30 % — 70 % |
30 % — 70 % |
30 % — 70 % |
|
|||||
Environmental friendly |
|||||
RoHS |
No excessive harmful substances |
No excessive harmful substances |
No excessive harmful substances |
No excessive harmful substances |
No hazardous substances above threshold values |
Standards and Specifications |
|||||
Connections are standard |
IEC 60947-7-1 |
IEC 60947-7-1 |
IEC 60947-7-1 |
IEC 60947-7-1 |
IEC 60947-7-1 |